The JA-82ST is used to detect fire hazards in the interior of residential or commercial buildings. It is not designed to be installed in industrial premises. The JA-82ST detector uses wireless communication.

JablotronJA-82ST wireless combined smoke and heat detector

JA-82ST – Jablotron
JA-82ST wireless combined smoke and heat detector Powiększ

JablotronJA-82ST wireless combined smoke and heat detector

JA-82ST – Jablotron
sztuk
Zaloguj się, aby zobaczyć cenę

The JA-82ST consists of two independent detectors – an optical smoke detector and a heat detector. The optical smoke detector works on the principle of scattered light and is very sensitive to large dust particles which are present in dense smoke. It is less sensitive to smaller particles generated by the combustion of liquids such as alcohol. That is why there is also a built-in heat detector which has a slower reaction but is much better at detecting fire which generates heat quickly with a small amount of smoke. The microprocessor performs digital analysis of these values which markedly increases false alarm immunity.

Specyfikacja

Power3 x AA 1.5V; 2.4Ah alkaline batteries
Typical lifetimeapprox. 3 years
Communication band868.5 MHz, OASiS protocol
Communication rangeapprox. 300 m (unrestricted area)
Dimensionsdiameter 126 mm, height 50 mm
Smoke detectionoptical light scattering
Smoke detector sensitivitym = 0.11 - 0.13 dB/m according to EN 54-7
Heat detectionclass A2 according to EN 54-5
Alarm temperature+60°C to +70°C
Operating temperature range-10°C to +80°C
Complies withEN 54-5, EN 54-7, EN 54-25
Also complies withETSI EN 300220, EN 50130-4, EN 55022, EN 60950-1
Can be operated according toERC REC 70-03